Plan Review Notes
Plan Review Notes For Permit 17031152
Permit Number 17031152
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-03 08:08:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031152
 4/3/17
  
 1) THE AC DUCT PLAN IS NOT COMPLETELY LEGIBLE AND NOT
 TO SCALE. REFER TO SECTION 107.2.4.1 WPB AMENDMENTS TO
 THE THE FBC AND PROVIDE A CLEAR. LEGIBLE PLAN USING A
 MINIMUM 1/8" SCALE.
  
 2) PLEASE IDENTIFY ALL ROOMS AND SPACES ON THE REVISED
 PLAN- SECTION 107.2.4.1.
  
 3) IF USING A FL. PRODUCT APPROVAL FOR ANCHORING CLIPS,
 PROVIDE A COMPLETE DOCUMENT THAT INCLUDES THE COVER
 SHEET AS SHOWN ON THE WEBSITE, AND PLEASE CIRCLE OR
 HIGHLIGHT ALL APPLICABLE DETAILS, NOTES, AND ANCHORING
 INSTRUCTIONS- RULE 9N-3 FAC.
  