Plan Review Notes
Plan Review Notes For Permit 17031144
Permit Number 17031144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-03 16:03:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET AC 1.00 - THERE IS A NOTE INDICATING EGRESS
 WINDOW INFORMATION. THERE IS ALSO A NOTE INDICATING A
 2' 2" X 50" WINDOW DIMENSION. THERE IS INSUFFICIENT
 INFOMATION DEMONSTRATING COMPLIANCE FOR EGRESS WINDOWS.
  
 PER NFPA 101, CHAPTER 16, NEW DAYCARE OCCUPANCIES
  
 16.2.11 SPECIAL MEANS OF EGRESS FEATURES.
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT
 LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH ALL OF THE FOLLOWING, UNLESS OTHERWISE
 PERMITTED BY 16.2.11.1.2:
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 IN. (510 MM) IN WIDTH, 24
 IN. (610 MM) IN HEIGHT, AND 5.7 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN. (1120 MM) ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 FT2 (0.5 M2) OPENING AND A DEPTH OF NOT
 LESS THAN 20 IN. (510 MM), TO PASS FULLY THROUGH THE
 OPENING.
  
 PLEASE PROVIDE SPECIFIC WINDOW DETAIL
 SHOWING/INDICATING COMPLIANCE WITH ALL 3 REQUIREMENTS.
  
  
  
  
 2)
 SHEET AC 1.00 - THERE IS NO DOOR SCHEDULE TO
 INDICATE/CONFIRM DOOR AND OPENING SIZE,INCLUDING
 BATHROOM DOORS, EXIT HARDWARE, LOCKS AND LATCHING, ETC.
  
 16.2.2.2 DOORS.
 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY
 DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE COMPLYING WITH 7.2.1.7.
 16.2.2.2.3 SPECIAL LOCKING ARRANGEMENTS.
 16.2.2.2.3.1 DELAYED-EGRESS LOCKING SYSTEMS COMPLYING
 WITH 7.2.1.6.1 SHALL BE PERMITTED.
 16.2.2.2.3.2 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES
 COMPLYING WITH 7.2.1.6.2 SHALL BE PERMITTED.
 16.2.2.2.3.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES
 LOCKING IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE
 PERMITTED.
 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR
 AREAS SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM
 INSIDE THE SPACE OR AREA.
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE
 READILY ACCESSIBLE TO THE STAFF.
  
 PLEASE PROVIDE SPECIFIC DETAILS MEETING THE
 REQUIREMENTS.
  
  
  
  
 3)
 SHEET AC 1.00 - THERE APPEARS TO BE A KITCHEN ROOM. ANY
 COOKING EQUIPMENT SHALL MEET THE REQUIRMETS OF NFPA 96
  
 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH 9.2.3, UNLESS OTHERWISE PERMITTED BY
 16.3.2.4 OR 16.3.2.5.
 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN FOOD PREPARATION AREAS AND DINING AREAS.
 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR
 FOOD WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED
 TO BE PROTECTED.
  
 PLEASE PROVIDE A NOTE WITH INTENTIONS OR COMPLIANCE.
  
  
  
 4)
 SHEET AC 1.00 - THERE IS AN INCORRECT"2015" REFERENCE
 TO THE CURRENT FFPC.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE, EFFECTIVE
 DECEMBER 31, 2014, INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
  
  
  
 5)
 SHEET AC 1.00 - THERE IS NO SITE PLAN SUBMITTED. A SITE
 PLAN IS REQUIRED SHOWING THE ENTIRE PROPERTY CONFIRMING
 ALL EXTS LEAD TO A PUBLIC WAY.
  
 16.2.7 DISCHARGE FROM EXITS. DISCHARGE FROM EXITS SHALL
 BE ARRANGED IN ACCORDANCE WITH SECTION 7.7.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH
 AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO
 A PUBLIC WAY.
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
  
  
 6)
 SHEET AC 1.00 - THERE IS A REFERENCE TO AN ELECRICAL
 SHEET FOR EMERGENCY LIGHTING. NO ELECTRICAL SHEET
 SUBMITTED.
  
  
  
 7)
 THRE IS NO INDICATIONS OF A FIRE ALARM
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST
 ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE
 OR TO AN EXTERIOR EXIT ACCESS BALCONY IN ACCORDANCE
 WITH 7.5.3, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM
 IN ACCORDANCE WITH SECTION 9.6.
 16.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM SHALL BE BY MANUAL MEANS AND BY OPERATION
 OF ANY REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER
 SYSTEMS. (SEE 16.3.4.5.)
  
  
 8)
 THERE IS INSUFFICEINT INFORMATION SUBMITTED TO COMPLETE
 A COMPHRENSIVE FIRE PLAN REVIEW. PLEASE ENSURE THAT THE
 SUBMITTAL MEETS ALL THE REQUIRMENTS OF THE FLORIDA
 STATUTUE AND THE FLORIDA FIRE PREVENTION CODE FOR NEW
 DAY CARES.
  
  
  
  
 9)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 10)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
  
 11)
 THIS BUILDING DOES NOT MEET THE REQUIREMENTS FOR
 OCCUPANCY AS A DAY CARE AND SHALL NOT BE OCCUPIED UNTIL
 IT DOES AND HAS PASSED ALL APPLICABLE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  