Plan Review Notes For Permit 17031136 |
Permit Number |
17031136 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-04-07 10:23:48 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17031136 | | 4/7/17 | | | | 1) SHEET 2.1: THE LEGEND INDICATES A 50 CFM KITCHEN | | EXHAUST FAN THAT IS NOT SHOWN ON THE PLAN. PLEASE NOTE | | THAT A MINIMUM 100 CFMS IS REQUIRED PER TABLE 403.3 IF | | THE EXHAUST IS OPERATED INTERMITTENTLY. | | | | 2) SHOW THE LOCATIONS OF THE COOKTOP EXHAUST FAN AND | | EXHAUST DUCT AND SUBMIT MANUFACTURER'S SPECIFICATIONS- | | SEE SECTION 505.2. | | | | 3) PROVIDE THE CFMS AT EACH NEW SUPPLY DIFFUSER. | | | | 4) PROVIDE EXHAUST FOR THE NEW DRYER. SHOW THE TYPE AND | | SIZE OF EXHAUST DUCT, THE DUCT RUN AND TERMINATION | | LOCATION, OR THE POINT OF CONNECTION TO THE EXISTING | | EXHAUST RISER. ADVISORY: EXHAUST DUCTS SHALL NOT EXTEND | | INTO OR RUN THROUGH PLENUMS- SECTION 504.4. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|