Plan Review Notes
Plan Review Notes For Permit 17031136
Permit Number 17031136
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-07 10:23:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031136
 4/7/17
  
 1) SHEET 2.1: THE LEGEND INDICATES A 50 CFM KITCHEN
 EXHAUST FAN THAT IS NOT SHOWN ON THE PLAN. PLEASE NOTE
 THAT A MINIMUM 100 CFMS IS REQUIRED PER TABLE 403.3 IF
 THE EXHAUST IS OPERATED INTERMITTENTLY.
  
 2) SHOW THE LOCATIONS OF THE COOKTOP EXHAUST FAN AND
 EXHAUST DUCT AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SEE SECTION 505.2.
  
 3) PROVIDE THE CFMS AT EACH NEW SUPPLY DIFFUSER.
  
 4) PROVIDE EXHAUST FOR THE NEW DRYER. SHOW THE TYPE AND
 SIZE OF EXHAUST DUCT, THE DUCT RUN AND TERMINATION
 LOCATION, OR THE POINT OF CONNECTION TO THE EXISTING
 EXHAUST RISER. ADVISORY: EXHAUST DUCTS SHALL NOT EXTEND
 INTO OR RUN THROUGH PLENUMS- SECTION 504.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER