Plan Review Notes
Plan Review Notes For Permit 17031136
Permit Number 17031136
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-04 11:12:46PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION.
  
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 1)
 SHEET 1.1 - THERE IS NO INDICATION OF A FIRE CODE
 REFERENCE AND/OR COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE ENSURE ALL WORK IS DONE IN COMPLIANCE WITH THE
 ABOVE NOTED CODE.
  
  
  
  
 2)
 SHEET 1.1 - THERE ARE INDICATIONS OF WALLS THAT ARE
 BEING REMOVED AND NEW WALLS INSTALLED (OR A RAISED
 CEILING).
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE WITH:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  