2017-04-04 12:25:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THE SUBMITTED CONSTRUCTION PLAN UNDER SCOPE OF WORK, |
| 1) INDICATES REMOVE (1) ADDRESSIBLE PULL STATION |
| LOCATED IN OPEN LOBBY. |
| |
| THERE IS NOTHING INDICATED ON THE FLOOR PLAN LAYOUT |
| RELATING TO A PULL STATION. |
| |
| PLEASE CORRECT. |
| |
| |
| |
| 2) THE PROPOSED REMOVAL OF A PULL STATION MAY BE A CODE |
| VIOLATION OF FLORIDA FIRE PREVENTION CODE AND NFPA 72. |
| |
| PULL STATIONS ARE REQUIRED WITHIN 5' OF THE EXIT DOOR. |
| |
| 17.14.5 MANUAL FIRE ALARM BOXES SHALL BE INSTALLED SO |
| THAT THEY ARE CONSPICUOUS, UNOBSTRUCTED, AND |
| ACCESSIBLE. |
| 17.14.6 MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN |
| 60 IN. (1.52 M) OF THE EXIT DOORWAY OPENING AT EACH |
| EXIT ON EACH FLOOR. |
| 17.14.7 MANUAL FIRE ALARM BOXES SHALL BE MOUNTED ON |
| BOTH SIDES OF GROUPED OPENINGS OVER 40 FT (12.2 M) IN |
| WIDTH, AND WITHIN 60 IN. (1.52 M) OF EACH SIDE OF THE |
| OPENING. |
| 17.14.8* ADDITIONAL MANUAL FIRE ALARM BOXES SHALL BE |
| PROVIDED SO THAT THE TRAVEL DISTANCE TO THE NEAREST |
| FIRE ALARM BOX WILL NOT BE IN EXCESS OF 200 FT (61.0 |
| M), MEASURED HORIZONTALLY ON THE SAME FLOOR. |
| |
| PLEASE PROVIDE THE JUSTIFICATION FOR THE REMOVAL OF THE |
| PULL STATION AND FIRE CODE REFERENCE ALLOWING IT TO BE |
| REMOVED. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |