2017-03-30 19:20:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LETTER FROM THE DURAPAX SALES MANAGER IS NOT
 ACCEPTABLE. THE LETTER CALLS FOR INSTALLING A TORCH
 APPLIED PLY OF DURAPAX SMOOTH POLYESTER APP DIRECTLY TO
 THE PRIMED CONCRETE DECK. THE APPROVED ASSEMBLY THAT
 YOU PROPOSE TO USE FROM NOA NO.13-1022.08, SYSTEM TYPE
 A, REQUIRES ALL LAYERS OF INSULATION TO BE HOT MOPPED
 DIRECTLY TO THE PRIMED CONCRETE DECK AND THE ROOF
 MEMBRANES ARE THEN HOT MOPPED OVER THE INSULATION. THE
 INSTALLATION CAN NOT DEVIATE FROM THE TESTED AND
 APPROVED ASSEMBLY. FBC 1504.1