Plan Review Notes For Permit 17031030 |
Permit Number |
17031030 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-30 12:46:33 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS | | JOB. PERMIT VALUE IS TO INCLUDE LABOR, MATERIALS, | | OVERHEAD, PROFIT, EVEN IF PROVIDED BY OTHERS. | | | | 2. REVISE PLAN TO INCLUDE EXISTING OCCUPANCY | | CLASSIFICATION. IT APPEARS THAT THIS IS A CHANGE OF | | OCCUPANCY, FROM A2 TO M; IS THIS CORRECT? IF THIS IS | | THE CASE, REVISE PLAN TO INCLUDE CHANGE OF OCCUPANCY | | AND SHOW COMPLIANCE WITH ALL REQUIREMENTS OF FBC EB | | CHAPTER 10. | | | | 3. LS201 PROJECT SUMMARY STATES THIS IS BUILDING TYPE | | IIB, BUT PERMIT RECORDS SHOW A PERMIT FOR TERMITE | | DAMAGE. CLARIFY WHAT WOOD WAS DAMAGED IN A NON | | COMBUSTIBLE BUILDING, FBC 107. | | | | 4. FBC A 202.4, SHOW THE ACCESSIBLE ROUTE FROM THE | | PUBLIC WAY AND FROM ACCESSIBLE PARKING. PROVIDE ENOUGH | | INFORMATION (CHANGES IN ELEVATION, SLOPES) TO SHOW | | COMPLIANCE. | | |
|