Plan Review Notes
Plan Review Notes For Permit 17030989
Permit Number 17030989
Review Stop E
Sequence Number 2
Notes
Date Text
2017-04-19 16:43:292ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 2ND REVIEW FBC 2014 EXISTING BUILDING
  
 RESULT FAIL - AN APPLICATION WAS SUBMITTED BUT NO
 INSPECTION REPORT WAS PROVIDED. PLEASE COMPLIY WITH THE
 REMAINING COMMENTS BELOW AS PROVIDED IN THE 1ST REVIEW.
  
 THIS APPLICATION IS TO RESOLVE WORK DONE WITHOUT A
 PERMIT AS DESCRIBED IN CE16060098. NO ELECTRICAL
 INFORMATION HAS BEEN PROVIDED. PLEASE HAVE THE PROPERTY
 INSPECTED BY A LICENSED ELECTRICIAN. THE ELECTRICIAN
 SHOULD INSPECT THE PROPERTY INCLUDING DESTRUCTIVE
 INSPECTION IF NEEDED AND BE PREPARED TO PROVIDE A
 REPORT SPECIFYING CORRECTIONS NEEDED AND FURTHER BE
 PREPARED TO CERTIFY COMPLIANCE WITH APPLICABLE
 REQUIREMENTS.
  
 IN ADDITION TO GENERAL CONFORMANCE TO THE REQUIREMENTS
 OF APPLICABLE CODE, THE FOLLOWING MAY BE REQUIRED IF
 NOT CURRENTLY PROVIDED.
  
 FBC- 107.3.5.3 SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBCRE 3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 FBCRE 3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 FBCE 3902.3 OUTDOOR RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 FBCRE 3902.1 BATHROOM RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 FBCE 3902.6 KITCHEN RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES THAT SERVE COUNTERTOP SURFACES SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 FBCE 3902.7 SINK RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF
 THE OUTSIDE EDGE OF A SINK THAT IS LOCATED IN AN AREA
 OTHER THAN A KITCHEN, SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP
 POSITION IN THE WORK SURFACES OR COUNTERTOPS.
  
 FBCRE 3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE 4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL