2017-04-19 16:43:29 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| 2ND REVIEW FBC 2014 EXISTING BUILDING |
| |
| RESULT FAIL - AN APPLICATION WAS SUBMITTED BUT NO |
| INSPECTION REPORT WAS PROVIDED. PLEASE COMPLIY WITH THE |
| REMAINING COMMENTS BELOW AS PROVIDED IN THE 1ST REVIEW. |
| |
| THIS APPLICATION IS TO RESOLVE WORK DONE WITHOUT A |
| PERMIT AS DESCRIBED IN CE16060098. NO ELECTRICAL |
| INFORMATION HAS BEEN PROVIDED. PLEASE HAVE THE PROPERTY |
| INSPECTED BY A LICENSED ELECTRICIAN. THE ELECTRICIAN |
| SHOULD INSPECT THE PROPERTY INCLUDING DESTRUCTIVE |
| INSPECTION IF NEEDED AND BE PREPARED TO PROVIDE A |
| REPORT SPECIFYING CORRECTIONS NEEDED AND FURTHER BE |
| PREPARED TO CERTIFY COMPLIANCE WITH APPLICABLE |
| REQUIREMENTS. |
| |
| IN ADDITION TO GENERAL CONFORMANCE TO THE REQUIREMENTS |
| OF APPLICABLE CODE, THE FOLLOWING MAY BE REQUIRED IF |
| NOT CURRENTLY PROVIDED. |
| |
| FBC- 107.3.5.3 SMOKE DETECTORS PURSUANT TO FBC-R |
| 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| |
| FBCRE 3901.2.1 SPACING. |
| RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| OUTLET. |
| |
| FBCRE 3703.2 KITCHEN AND DINING AREA RECEPTACLES. |
| A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL |
| BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE |
| OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, |
| DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN |
| COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF |
| TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF |
| WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER |
| RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY, |
| BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS |
| FOR REFRIGERATION APPLIANCES. |
| |
| FBCE 3902.3 OUTDOOR RECEPTACLES. |
| ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| |
| FBCRE 3902.1 BATHROOM RECEPTACLES. |
| ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE |
| GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| |
| FBCE 3902.6 KITCHEN RECEPTACLES. |
| ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES THAT SERVE COUNTERTOP SURFACES SHALL HAVE |
| GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| |
| FBCE 3902.7 SINK RECEPTACLES. |
| ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF |
| THE OUTSIDE EDGE OF A SINK THAT IS LOCATED IN AN AREA |
| OTHER THAN A KITCHEN, SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP |
| POSITION IN THE WORK SURFACES OR COUNTERTOPS. |
| |
| FBCRE 3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| |
| FBCRE 4002.14 TAMPER-RESISTANT RECEPTACLES. |
| IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| TAMPER-RESISTANT RECEPTACLES. |
| |
| PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| & FBC 117. |
| FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A |
| PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| PURPOSES UNTIL APPROVED. |
| FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| |
| |
| STEVEN KENNEDY, CBO |
| ASSISTANT BUILDING OFFICIAL |
| (561) 805-6710 |
| [email protected] |
| |