2017-04-12 15:19:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET SK 1 - THERE IS AN INDICATION OF A FUEL TANK
 WHILE SHEET E 1 COMMENT NOTE # 5 INDICATES NATURAL GAS.
  
 CONFLICT, PLEASE CORRECT OR CLARIFY.
  
  
  
 2) INFORMATION REQUEST - WILL THIS GENERATOR SUPPLY
 BACK-UP POWER TO A FIRE ALARM OR OTHER LIFE SAFETY
 SYSTEM?
  
 PROVIDE APPLICABLE NOTE
  
  
  
 3) IF YES TO # 2, PLEASE ENSURE COMPLIANCE WITH NFPA
 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
 2010 EDITION
  
 PROVIDE APPLICABLE NOTE
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  