Plan Review Notes
Plan Review Notes For Permit 17030945
Permit Number 17030945
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-23 14:29:20THE BACKFLOW DEVICE IS REQUIRED TO BE LEAD FREE PER THE
 CITY OF WPB CROSS -CONNECTION CONTROL MANUAL & 2014
 FBC-PLUMBING SEC. 605.2.1. THE SUBMITTED DOCUMENTS DO
 NOT SHOW THAT THE DEVICE IS LEAD FREE.
  
 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
  
 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS
 SHALL BE ON THE JOBSITE FOR INSPECTION.
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  