2017-03-27 15:48:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 THE SUBMITTED APPLICATION INDICATES AS-BUILT FIRE
 SPRINKLER PLANS AND THE SUBMITTED PLAN SHEET INDICATES
 AS BUILT; HOWEVER, THE SUBMITTED PLAN SHEET(S) DOES NOT
 (DO NOT) INDICATE ANY CLOUD REVISIONS, CALL OUTS AND/OR
 NOTES INDICATING WHAT AREAS, DEVICES, HEADS, PIPING,
 ETC IS AS-BUILT OR REVISED FROM THE MASTER PERMIT.
  
 PER NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE CLEARLY INDICATE THE EACH AREA OR PIECE OF
 EQUIPMENT REVISED/AS-BUILT ON THE PLAN SHEETS.
  
  
  
 2)
 THE SUBMITTED SHEETS WERE NOT BOUND TOGETHER OR
 ORGAINZED SO THEY CAN NOT SEPARATE.
  
 PLEASE BIND AND/OR STAPLE YOUR SUBMITTED PLAN SHEETS
 INTO ORGANIZED SETS.
  
  
  
 3)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 4)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
  
  