Plan Review Notes
Plan Review Notes For Permit 17030927
Permit Number 17030927
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-30 11:14:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DETAIL 1-S5.001, OTHER LOCATIONS, STRUCTURAL
 SHEATHING SHOWN. REVISE PLAN TO SHOW COMPLIANCE WITH
 FBC B 603.1 (COMBUSTIBLES ALLOWED).
  
 2. G2.001 DOES NOT ADDRESS THE SMOKE CONTROL AND/OR
 ELEVATOR PRESSURIZATION. NO ELEVATOR LOBBIES ARE SHOWN
 AS EXISTING OR PROPOSED AND AN ATRIUM IS SHOWN. REVISE
 PLAN TO ADDRESS (FUNCTIONAL EXISTING SYSTEMS TO
 REMAIN?)
  
 3. G2.001 STATES THAT EXISTING OCCUPANT LOAD IS "TO
 REMAIN." PROVIDE THE OCCUPANT LOAD, FBC 107. THIS
 INFORMATION IS REQUIRED FOR C.O., COMPLIANCE WITH FBC
 EB 805, FBC B CHAPTER 10.
  
 4. 01-G2.001 SHOWS (EXISTING) EXITING THROUGH A LOADING
 ZONE. FBC 107, CODE COMPLIANCE SHOULD BE CLEAR TO
 SOMEONE UNFAMILIAR WITH THE BUILDNG. ALTHOUGH
 "EXISTING", IT IS NOT CLEAR WHETHER EXITING THROUGH A
 MORE HAZARDOUS AREA WAS ALLOWED WHEN THE BUILDING WAS
 PERMITTED. REVISE PLAN TO CLARIFY. INCLUDE A NORTH
 ARROW. IT IS NOT CLEAR IF THIS IS THE ALLEY OR ANOTHER
 AREA WHICH IS NOT VISIBLE ON PICTOMETRY AND OTHER
 AERIALS.
  
 5. S0.00 RAILINGS, REVISE DESIGN CRITERIA TO INCLUDE
 ALL REQUIREMENTS OF FBC B 1607.8.
  
 6. THIS PERMIT WILL BE ISSUED WITH PROVISO, ENGINEERING
 AND SHOP DRAWINGS FOR RAILINGS REQUIRED AT INSPECTION.
 SUBJECT TO INSPECTOR'S DISCRETION, THIS MAY BE REQUIRED
 TO BE SUBMITTED FOR PLAN REVIEW. DOR TO REVIEW
 DELEGATED ENGINEERING AND SHOPS PRIOR TO INSPECTION
 AND/OR SUBMITTAL.
  