2017-07-17 10:42:444TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 7/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CORRECTED AC PLANS INDICATE THEY WERE DRAWN BY
 THE COMPANY THAT PREPARED THE AC CALCULATIONS- ENERGY
 HOUSE TECHNOLOGY. PLEASE NOTE THAT ENERGY HOUSE
 TECHNOLOGY CANNOT DRAW THE AC PLAN FOR THE HOUSE UNLESS
 THE COMPANY IS FL. STATE LICENSED AS AN AC OR
 MECHANICAL CONTRACTOR, AND IS THE INSTALLING CONTRACTOR
 ON THE PROJECT- SECTION 105.3.1 WEST PALM BEACH
 AMENDMENTS TO THE FBC. I PERFORMED A LICENSE SEARCH ON
 THE DPBR WEBSITE AND NO CONTRACTORS LICENSE EXISTS FOR
 EITHER ENERGY HOUSE TECHNOLOGY OR THE COMPANY OWNER
 BRUCE TSCHOSIK.
  
 2) PLEASE PROVIDE DUPLICATE COPIES OF THE AC
 CALCULATIONS FOR LEVELS 1 & 2- ONLY ONE SET WAS
 SUBMITTED.
  
 3) THE SUBMITTAL FOR THE HURRICANE PAD INDICATES AN
 INCORRECT WIND SPEED OF 150 MPH WHICH IS DEFICIENT FOR
 WEST PALM BEACH THE CORRECT ULTIMATE DESIGN WIND SPEED
 FOR RISK CATEGORY II STRUCTURES IN WPB IS 170 MPH-
 SECTION 1609 FBC-14 BUILDING.
  