Plan Review Notes
Plan Review Notes For Permit 17030764
Permit Number 17030764
Review Stop M
Sequence Number 3
Notes
Date Text
2017-06-07 08:12:133RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 6/7/17
  
 RESULTS: DENIED.
  
 1) COMMENTS FROM THE PREVIOUS REVIEWS STILL EXIST-
 PLEASE SEE REPRINTED COMMENTS BELOW AND COMPLY.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 5/8/17
  
 RESULTS: DENIED.
 PLEASE ADDRESS THE COMMENTS LISTED BELOW.
  
 1) THE ENERGY FORM R405-2014 MUST BE SIGNED AND DATED
 BY THE OWNER/AGENT.
  
 2) THE CLIMATE ZONE 2 LISTED ON FORM R405 IS INCORRECT:
 PALM BEACH COUNTY IS CLIMATE ZONE 1A- SEE TABLE R301.1
 FBC-14 ENERGY CONSERVATION.
  
 3) COMMENTS #3- #7 FROM THE1ST REVIEW STILL EXIST. SEE
 THE REPRINTED LIST BELOW:
  
 1ST REVIEW
  
 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW
 AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC
 EQUIPMENT SCHEDULE.
  
 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE-
 IT IS NOT APPLICABLE TO THIS PROJECT.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  