Plan Review Notes For Permit 17030764 |
Permit Number |
17030764 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-06-07 08:12:13 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #17030764 | | 6/7/17 | | | | RESULTS: DENIED. | | | | 1) COMMENTS FROM THE PREVIOUS REVIEWS STILL EXIST- | | PLEASE SEE REPRINTED COMMENTS BELOW AND COMPLY. | | | | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17030764 | | 5/8/17 | | | | RESULTS: DENIED. | | PLEASE ADDRESS THE COMMENTS LISTED BELOW. | | | | 1) THE ENERGY FORM R405-2014 MUST BE SIGNED AND DATED | | BY THE OWNER/AGENT. | | | | 2) THE CLIMATE ZONE 2 LISTED ON FORM R405 IS INCORRECT: | | PALM BEACH COUNTY IS CLIMATE ZONE 1A- SEE TABLE R301.1 | | FBC-14 ENERGY CONSERVATION. | | | | 3) COMMENTS #3- #7 FROM THE1ST REVIEW STILL EXIST. SEE | | THE REPRINTED LIST BELOW: | | | | 1ST REVIEW | | | | 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW | | AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC | | EQUIPMENT SCHEDULE. | | | | 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE- | | IT IS NOT APPLICABLE TO THIS PROJECT. | | | | 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR | | HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL. | | | | 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER- | | SECTION M1305.1.4.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|