2017-03-23 09:49:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 3/23/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MINI-SPLIT SYSTEM- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR
 THE EXISTING RESIDENCE INDICATES BUILDING 2 HAS NO
 HEATING OR AIR CONDITIONING, THEREFORE NOW THAT IT IS
 BEING CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE
 IS REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS
 OUTLINED IN SECTIONS R101.5.1.1.
  
 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW
 AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC
 EQUIPMENT SCHEDULE.
  
 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE-
 IT IS NOT APPLICABLE TO THIS PROJECT.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 7) PROVIDE ELECTRICAL PLANS.
  