Notes
Date Text
2017-03-21 09:08:47PLEASE CLARIFY IF HOT TUB IS NEW? IF SO A REVISED LOAD
 CALCULATION WILL NEE TO BE SUBMITTED. ALSO WHAT IS THE
 MAIN BREAKER SIZE?
  
 GFCI PROTECTION REQUIRED FOR HOT TUB. PROVIDE A NOTE
 AND BREAKER SIZE FEEDING THIS UNIT
  
 PER FBC RES 315 WHEN A PERMIT OCCURS AT A RESIDENCE
 SMOKE DETECTORS ARE TO BE INSTALLED IF NOT EXISTING.
 PLEASE NOTE ON PLANS IF THE ARE EXISTING..
  