2017-03-23 08:55:29 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17030678 |
| 3/23/17 |
| |
| 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW TRANE SYSTEM- SECTION R403.6.1 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY |
| CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR |
| THE EXISTING RESIDENCE INDICATES NO HEATING OR AIR |
| CONDITIONING, THEREFORE NOW THAT IT IS BEING |
| CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE IS |
| REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS |
| OUTLINED IN SECTIONS R101.5.1.1. |
| |
| 3) IT APPEARS BY THE DRAWING THAT THE AIR HANDLER IS IN |
| THE ATTIC. PLEASE SECTION R403.2.4 FBC-14 ENERGY AND |
| SHOW COMPLIANCE WITH ITEMS 1-4. |
| |
| 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL. |
| |
| 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE |
| CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER- |
| SECTION M1305.1.4.1. |
| |
| 6) PLEASE LABEL ALL ROOMS AND SPACES ON THE DUCT LAYOUT |
| PLAN. |
| |
| 7) THE 12X4" RETURN TRANSFER GRILLS FOR THE BEDROOMS |
| ARE UNDERSIZED PER SECTION M1602.4- 50 SQ. INCHES OF |
| FREE AIR PER 100 CFMS REQUIRED. |
| |
| 8) PROVIDE ELECTRICAL PLANS. |
| |
| 9) BECAUSE OF THE NEW EXTERIOR CONDENSER INSTALLATION, |
| THE PLAN HAS BEEN FORWARDED TO PLANNING AND ZONING FOR |
| REVIEW. |
| |