2017-03-23 08:55:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030678
 3/23/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW TRANE SYSTEM- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR
 THE EXISTING RESIDENCE INDICATES NO HEATING OR AIR
 CONDITIONING, THEREFORE NOW THAT IT IS BEING
 CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE IS
 REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS
 OUTLINED IN SECTIONS R101.5.1.1.
  
 3) IT APPEARS BY THE DRAWING THAT THE AIR HANDLER IS IN
 THE ATTIC. PLEASE SECTION R403.2.4 FBC-14 ENERGY AND
 SHOW COMPLIANCE WITH ITEMS 1-4.
  
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 6) PLEASE LABEL ALL ROOMS AND SPACES ON THE DUCT LAYOUT
 PLAN.
  
 7) THE 12X4" RETURN TRANSFER GRILLS FOR THE BEDROOMS
 ARE UNDERSIZED PER SECTION M1602.4- 50 SQ. INCHES OF
 FREE AIR PER 100 CFMS REQUIRED.
  
 8) PROVIDE ELECTRICAL PLANS.
  
 9) BECAUSE OF THE NEW EXTERIOR CONDENSER INSTALLATION,
 THE PLAN HAS BEEN FORWARDED TO PLANNING AND ZONING FOR
 REVIEW.
  