Plan Review Notes
Plan Review Notes For Permit 17030677
Permit Number 17030677
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-23 09:23:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030677
 3/23/17
  
 1) SUBMIT TWO COPIES OF THE WPB CONSTRUCTION SERVICES
 AC CHANGE OUT FORM.
  
 2) PROVIDE A CONDENSATE DISPOSAL PLAN.
  
 3) PROVIDE CONDENSER TIE-DOWN DETAILS TO MEET WIND LOAD
 AND PRESSURES..
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved