2017-04-26 10:35:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030438
 4/26/17
  
 1) THE 3.8 KW HEATING CAPACITIES IN AHU'S- 1 & 2 ARE
 UNDERSIZED PER THE NEW SUBMITTED AC COOLING AND HEATING
 CALCULATIONS- SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION. A MINIMUM OF 6 AND 7.5 KW HEATERS ARE
 REQUIRED.
  
 2) SHEET M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF THE NEW AHU'S. PROVIDE SYMBOLS ON
 THE PLAN TO SHOW THE LOCATIONS OF THE DEVICES, AND
 INDICATE HOW THEY WILL BE SUPERVISED- SEE SECTIONS
 606.2.1, AND 606.4.1 FBC-14 MECHANICAL.
  
 3) M-1: PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS FOR
 THE O/A INTAKES AS OUTLINED IN SECTION 401.4, AND FOR
 THE EXHAUST OUTLETS AS OUTLINED IN SECTION 501.3.1.
  
 4) SUBMIT TWO COPIES OF THE MIAMI- DADE NOA FOR THE O/A
 LOUVERS.
  
 5) PLASE ATTACH THE MEP PLAN SETS TO THE MAIN
 ARCHITECTURAL PLANS. FAILURE TO RETURN TWO COMPLETE,
 CORRECTED, AND COLLATED SETS OF PLANS WILL RESULT IN A
 FAILED PLAN REVIEW.
  