2017-03-28 17:14:521ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A-2
 A) SHOW COMPLIANCE WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
 B) GRAB BARS ARE SHOWN AT 2 DIFFERENT HEIGHTS UNDER
 STAND ELEV DIAGR IT SHOWS 34" IN DETAIL 3+4 IT SHOWS
 36" MEASURED TO CENTER OF GRAB BAR WHICH DOES NOT
 COMPLY WITH FBC ACC 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 C) THE GRAB BAR ON SIDE WALL SHOWS 17" FROM REAR WALL
 IT SHALL COMPLY WITH FBC ACC 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 D) DOORS SHALL NOT SWING INTO BATHROOM UNLESS THEY MEET
 THIS EXCEPTION FBC ACC 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS:
 WHERE THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL
 USE AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE.
  
 2. SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 3. A WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE 403.1
  
 4. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT THIS
 TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  