Plan Review Notes
Plan Review Notes For Permit 17030670
Permit Number 17030670
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-03-22 11:04:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET LS 1 - PATHS OF TRAVEL ARE INDICATED; HOWEVER, IS
 THERE A PROPOSED FLOOR LAYOUT WITH ISLES AND/OR
 SHELVING OR IS THIS JUST A WHITE BOX?
  
 PLEASE PROVIDE APPLICBALE NOTE OF SHOW CHANGES.
  
  
  
 2)
 SHEET LS 1 - UNDER GENERAL NOTES IT IS UNCLEAR OF THE
 TYPE OF CONSTRUCTION AND THE OCCUPANCY.
  
 PLEASE CLARIFY AND/OR CORRECT.
  
  
  
 3)
 SHEET LS 1 - THERE IS NO OCCUPANCY LOAD INDICATED ON
 THIS SHEET. IT IS INDICATED ON A 1 BUT, IT APPEARS TO
 BE INCORRECT. IT SHOULD READ 113 AND BE INDICATED ON
 THE LS SHEET.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA
 ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR
 THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE
 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND
 NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING
 DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS
 SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE
 NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE
 USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
 PLEASE REVIEW GROSS FLOOR AREA, CORRECT THE COUNT AND
 ADD TO LS 1.
  
  
  
 4)
 SHEET A 3 - A DOOR SCHEDULE IS INDICATED; HOWEVER, THE
 EXISTING DOORS, DOOR HARDWARE AND LOCKS ARE NOT
 INCLUDED.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE INACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, SUCH
 HARDWARE SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN
 ONE-HALF OF THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM), AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE
 FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM), AND NOT MORE THAN 48 IN. (1220 MM), ABOVE
 THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED 15 LBF (66 N) ACTUATES THE CROSS BAR OR
 PUSH PAD AND LATCHES. 7.2.1.7.2 ONLY APPROVED PANIC
 HARDWARE SHALL BE USED ON DOOR ASSEMBLIES THAT ARE NOT
 FIRE-RATED DOOR ASSEMBLIES. ONLY APPROVED FIRE EXIT
 HARDWARE SHALL BE USED ON FIRE-RATED DOOR ASSEMBLIES.
 NEW PANIC HARDWARE AND NEW FIRE EXIT HARDWARE SHALL
 COMPLY WITH ANSI/UL 305, STANDARD FOR SAFETY PANIC
 HARDWARE, AND ANSI/BHMA A156.3, EXIT DEVICES.
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN DETENTION AND CORRECTIONAL
 OCCUPANCIES AS OTHERWISE PROVIDED IN CHAPTERS 22 AND
 23, SHALL NOT BE EQUIPPED WITH ANY LOCKING DEVICE, SET
 SCREW, OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE
 OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING
 DEVICE.
  
 PLEASE INCLUDE ALL EXISITN DOOR, HARDWARE AND LOCKS IN
 THE SCHEDULE AND ENSURE THEY COMPLY WITH NFPA 101.
  
  
  
  
 5)
 SHEET A 1 - A RAMP IS INDICATED. RAILING AND/OR GUARDS
 ARE NOT INDICATED.
  
 7.2.5 RAMPS.
 7.2.5.1 GENERAL. EVERY RAMP USED AS A COMPONENT IN A
 MEANS OF EGRESS SHALL CONFORM TO THE GENERAL
 REQUIREMENTS OF SECTION 7.1 AND TO THE SPECIAL
 REQUIREMENTS OF 7.2.5.
 7.2.5.2 DIMENSIONAL CRITERIA. THE FOLLOWING DIMENSIONAL
 CRITERIA SHALL APPLY TO RAMPS:
 (1) NEW RAMPS SHALL BE IN ACCORDANCE WITH TABLE
 7.2.5.2(A), UNLESS OTHERWISE PERMITTED BY THE
 FOLLOWING:
 (A) TABLE 7.2.5.2(A) SHALL NOT APPLY TO INDUSTRIAL
 EQUIPMENT ACCESS AREAS AS PROVIDED IN 40.2.5.2.
 (B) THE MAXIMUM SLOPE REQUIREMENT SHALL NOT APPLY TO
 RAMPS IN ASSEMBLY OCCUPANCIES AS PROVIDED IN CHAPTER
 12.
 (C) THE MAXIMUM SLOPE OR MAXIMUM RISE FOR A SINGLE RAMP
 RUN SHALL NOT APPLY TO RAMPS PROVIDING ACCESS TO
 VEHICLES, VESSELS, MOBILE STRUCTURES, AND AIRCRAFT.
 (2) EXISTING RAMPS SHALL BE PERMITTED TO REMAIN IN USE
 OR BE REBUILT, PROVIDED THAT THEY MEET THE REQUIREMENTS
 SHOWN IN TABLE 7.2.5.2(B), UNLESS OTHERWISE PERMITTED
 BY ANY OF THE FOLLOWING:
 (A) THE REQUIREMENTS OF TABLE 7.2.5.2(B) SHALL NOT
 APPLY TO INDUSTRIAL EQUIPMENT ACCESS AREAS AS PROVIDED
 IN 40.2.5.2.
 (B) THE MAXIMUM SLOPE OR MAXIMUM HEIGHT BETWEEN
 LANDINGS FOR A SINGLE RAMP RUN SHALL NOT APPLY TO RAMPS
 PROVIDING ACCESS TO VEHICLES, VESSELS, MOBILE
 STRUCTURES, AND AIRCRAFT.
 (C) APPROVED EXISTING RAMPS WITH SLOPES NOT STEEPER
 THAN 1 IN 6 SHALL BE PERMITTED TO REMAIN IN USE.
 (D) EXISTING RAMPS WITH SLOPES NOT STEEPER THAN 1 IN 10
 SHALL NOT BE REQUIRED TO BE PROVIDED WITH LANDINGS.
  
 7.2.5.4 GUARDS AND HANDRAILS.
 7.2.5.4.1 GUARDS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED FOR RAMPS, UNLESS OTHERWISE PROVIDED IN
 7.2.5.4.4.
 7.2.5.4.2 HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED ALONG BOTH SIDES OF A RAMP RUN WITH A RISE
 GREATER THAN 6 IN. (150 MM), UNLESS OTHERWISE PROVIDED
 IN 7.2.5.4.4.
 7.2.5.4.3 THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE
 MEASURED VERTICALLY TO THE TOP OF THE GUARD OR RAIL
 FROM THE WALKING SURFACE ADJACENT THERETO.
 7.2.5.4.4 THE REQUIREMENTS OF 7.2.5.4.1 AND 7.2.5.4.2
 SHALL NOT APPLY TO GUARDS AND HANDRAILS PROVIDED FOR
 RAMPED AISLES IN ASSEMBLY OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAPTERS 12 AND 13.
  
 PLEASE CLARIFY IF ANY RALINGS OR GUARD SHALL BE
 INSTALLED AND/OR CORRECT.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  