2017-03-21 16:37:051ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030643
 3/21/17
  
 1) M-1: THE PLAN IS INDICATING AN ALTERATION TO AN
 EXISTING SMOKE CONTROL SYSTEM HOWEVER IT DOES NOT
 APPEAR THAT THE CORRIDORS ARE ENCLOSED WITH PROPERLY
 CONSTRUCTED SMOKE BARRIERS IN ACCORDANCE WITH SECTIONS
 709 AND 909.5 FBC-14 BUILDING. PLEASE INDICATE THE
 MINIMUM PRESSURE DIFFERENCE REQUIRED ACROSS THE SMOKE
 BARRIER AND CLARIFY IF A RATIONAL ANALYSIS WAS USED TO
 ESTABLISH THE REQUIRED PRESSURES, AND TO ALSO SIZE THE
 DUCTS AND DIFFUSERS PROVIDING THE AIR- SEE SECTIONS
 909.4 AND 909.6.
  
 2) M-1: THE PLAN SHOWS SOME INCONSISTENCIES IN FLEX
 DUCT SIZING FOR THE DIFFUSERS SUPPLYING 250 AND 225
 CFMS. IN SOME ROOMS AND SPACES AN 8" DUCT IS USED, AND
 IN OTHERS A 10" DUCT.
  
 3) THE ENERGY FORM C402 MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER