2017-03-21 18:11:43 | 03/21/17 DISCUSSED COMMENTS WITH ROBERT BROWN. OK TO |
| SEND COMMENTS TO CONTRACTOR. |
2017-03-20 18:59:16 | |
| |
| |
| |
| RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- CONTRACTOR'S RE-ROOF PROPOSAL SUBMITTED VIA E-MAIL |
| ON 03/20/17: |
| THE ESTIMATED VALUE OF $49,500 IS TOO LOW. THE |
| VALUATION SHALL BE THE INDUSTRY'S FAIR MARKET VALUE |
| THAT INCLUDES ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES |
| (WHEN REQUIRED). SEC. 109.3 CITY AMENDMENTS. |
| THE CITY USES THE "MARSHALL & SWIFT" VALUATION SERVICE |
| AS A REFERENCE FOR ESTIMATING THE COST OF THE PROJECTS. |
| BASED ON THE MARSHALL & SWIFT VALUATION SERVICE THE |
| ESTIMATED AVERAGE COST TO INSTALL CONCRETE TILE IS |
| $5.79 PER SQUARE FOOT. THIS COST IS FOR NEW TILE |
| INSTALLATION ONLY. THE ESTIMATED VALUE TO INSTALL 8,500 |
| S.F. OF TILE IS $49,215. THEN, YOU NEED TO ADD THE COST |
| FOR ROOFING MATERIALS REMOVAL AND DISPOSAL, ROOF |
| SHEATHING REPLACEMENT, FASCIA REPLACEMENT, ROOF TO WALL |
| CONNECTIONS AND REPLACE SKYLIGHTS AS SPECIFIED ON THE |
| PROPOSAL SUBMITTED. |
| IN ADDITION, IT LOOKS LIKE THIS HOUSE HAS A FLAT ROOF. |
| THERE IS NOT INFORMATION ABOUT THE RE-ROOFING THIS |
| AREA. IF THIS AREA NEEDS TO BE RE-ROOF, THEN PRODUCT |
| APPROVAL AND COMPLETE INFORMATION FOR THE SELECTED FLAT |
| ROOF ASSEMBLY IS REQUIRED. |
| THEREFORE, THE COST TO RE-ROOF THIS HOUSE IS WELL |
| BEYOND THE $50,000. SEC. 105.15 CITY AMENDMENTS |
| REQUIRES THAT WHEN ANY WORK WITH A VALUE OF $50,000 OF |
| MORE ON A HOUSE THAT IS VALUED AT $750,000 OR MORE |
| NEEDS TO HAVE HURRICANE OPENING PROTECTION (SHUTTERS OR |
| DOORS/WINDOWS WITH IMPACT GLAZING). NEED TO PROVIDE |
| PROOF OF OPENINGS PROTECTION. |
| |
| NOTE: |
| BASED ON THE CITY RECORDS A PERMIT APPLICATION WAS |
| SUBMITTED LAST YEAR BY ANOTHER ROOFING CONTRACTOR TO |
| RE-ROOF THIS HOUSE. THAT PERMIT NEVER GOT ISSUED. THE |
| VALUATION DECLARED IN LAST YEAR PERMIT APPLICATION WAS |
| $57,260. THE VALUATION DECLARED IN THE CURRENT PERMIT |
| APPLICATION IS $59,500. THE VALUATION ON BOTH PERMIT |
| APPLICATIONS ARE CONSISTENT AND SEEMS TO BE FAIR MARKET |
| VALUE. |
| |
| LAST YEAR PERMIT APPLICATION NUMBER IS 16050988 AND |
| BELOW WERE THE PLAN REVIEW COMMENTS ON THAT PERMIT |
| APPLICATION: |
| |
| RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- THE VALUE OF THE HOUSE IS MORE THAN $750.000 AND |
| THIS HOUSE WAS BUILT BEFORE THE FLORIDA BUILDING CODE |
| WAS IN EFFECT. OPENING PROTECTION IS REQUIRED BY SEC. |
| 105.15 CITY AMENDMENTS. SEE COPY OF CITY AMENDMENT |
| BELOW. PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE |
| WINDOWS AND DOORS OPENING PROTECTION. |
| |
| 105.15 OPENING PROTECTION. |
| WHEN ANY ACTIVITY REQUIRING A BUILDING PERMIT THAT IS |
| APPLIED FOR ON OR AFTER JULY 1, 2008, AND FOR WHICH THE |
| ESTIMATED COST IS $50,000 OR MORE FOR A SITE BUILT |
| SINGLE-FAMILY DETACHED RESIDENTIAL STRUCTURE THAT IS |
| LOCATED IN THE WIND BORNE DEBRIS REGION AS DEFINED IN |
| THIS CODE AND THAT HAS AN INSURED VALUE OF $750,000 OR |
| MORE, OR, IF THE SITE BUILT SINGLE-FAMILY DETACHED |
| RESIDENTIAL STRUCTURE IS UNINSURED OR FOR WHICH |
| DOCUMENTATION OF INSURED VALUE IS NOT PRESENTED, HAS A |
| JUST VALUATION FOR THE STRUCTURE FOR PURPOSES OF AD |
| VALOREM TAXATION OF $750,000 OR MORE; OPENING |
| PROTECTIONS AS REQUIRED WITHIN THIS CODE OR FLORIDA |
| BUILDING CODE, RESIDENTIAL FOR NEW CONSTRUCTION SHALL |
| BE PROVIDED. |
| |
| EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES |
| PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT |
| REQUIRED TO COMPLY WITH THIS SECTION. |
| |
| 2- FLAT ROOF: |
| PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| REQUIRED BY GENERAL LIMITATION #7 OF NOA 14-0224.03 |
| SUBMITTED. CALCULATIONS REQUIRED TO MEET THE DESIGN |
| PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES ) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR THE ROOF VENTS TO BE INSTALLED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |