Plan Review Notes
Plan Review Notes For Permit 17030470
Permit Number 17030470
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-15 19:03:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS
 ARE INCORRECT FOR EXPOSURE C AND A WIND SPEED OF 170
 MPH VULT. SUBMIT CALCULATIONS FROM THE ENGINEER SHOWING
 HOW THE SPECIFIED WINDOW AND DOOR PRESSURES WERE
 DETERMINED. FBC 107.2.1.3
  
 2) FBC-R310.1 REQUIRES EACH SLEEPING ROOM TO HAVE AN
 EMERGENCY ESCAPE AND RESCUE OPENING. SPECIFY THE
 WINDOWS THAT ARE LOCATED IN THE SLEEPING ROOMS,
 IDENTIFY THE EXISTING WINDOWS TYPE AND INDICATE HOW YOU
 WILL COMPLY. ALSO SEE FBC EXISTING BUILDING SECTION
 704.1
  
 3) SUBMIT A COPY OF THE SIGNED CONTRACT TO VERY THE
 VALUE OF THE WORK. FBC 109.3