2017-03-14 12:00:581) INDICATE THE REQUIRED FIRE RATING OF THE STAIRWAY ON
 THE DRAWINGS.FROM THE ORIGINAL DRAWINGS THIS IS A 2
 HOUR RATED STAIRWAY.
 2) INDICATE THE FIRE RATING OF THE ENCLOSURE FOR THE
 PIPING ON THE DRAWINGS. THE DRAWINGS NOTE 2 LAYERS OF
 5/8 INCH TYPE X DRYWALL ON METAL STUD FRAMING WHICH
 WOULD PROVIDE AN 80 MINUTE FIRE RATING WHICH IS LESS
 THAN THE 2 HOUR RATING OF THE ENCLOSURE.THIS PIPING
 ENCLOSURE SHALL BE THE SAME RATING AS THE ENCLOSURE IN
 WHICH IT IS LOCATED.FBC 713..4, 713.5.
 3) INDICATE THE GAUGE OF THE METAL STUDS BEING USED.
  