Plan Review Notes For Permit 17030447 |
Permit Number |
17030447 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-16 10:06:31 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THIS STRUCTURE IS LOCATED IN WITHIN 600 FEET OF THE | | INTERCOASTAL WATERWAY AND IS CLASSIFIED AS EXPOSURE | | CATEGORY D. PLEASE REVISE THE COMPONENT AND CLADDING | | PRESSURES ACCORDINGLY. FBC 1609.4.3 | | | | 2) THE MEAN ROOF HEIGHT OF THE BUILDING AND NOT THE | | HEIGHT OF THE OPENING IS USED TO DETERMINE THE REQUIRED | | WINDLOAD PRESSURES FOR THE WINDOWS. FBC 1609.6.4.4.1 | | | | 3) IN ORDER TO DETERMINE IF THE REQUIREMENTS OF FBC | | 1029 FOR EMERGENCY ESCAPE AND RESCUE AND THE FBC | | EXISTING BUILDING 704.1 ARE IN COMPLIANCE, SPECIFY THE | | TYPE OF WINDOWS THAT ARE BEING REPLACED ( SINGLE HUNG, | | AWNING, ETC.) IN THE SLEEPING ROOMS. |
|