Plan Review Notes
Plan Review Notes For Permit 17030438
Permit Number 17030438
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-29 07:14:38CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
  
 NEED TO SHOW LOCATION OF THE METER, IS METER CT OR
 VOLTAGE.
 FAULT CURRENT CALCULATION AND SIGNAGE NEC 110.24(A)(B)
 NO GROUNDING SHOWN FOR THE SERVICE.
 ENERGY CALCULATION FBC EC C405.5.2
  
  