Plan Review Notes
Plan Review Notes For Permit 17030358
Permit Number 17030358
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-03-13 09:37:45PERMIT # 17030358
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
 1) ALL GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS
 LOCKS, PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY
 ACCESS.. KNOX LOCKS CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 2) PROVIDE AND MAINTAIN CLEAR AND UNOBSTRUCTED ACCESS
 TO ALL FIRE HYDRANTS AND FDC CONNECTIONS.
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7?-6? TO THE FRONT AND
 SIDES AND 4?-0? TO THE BACKSIDE OF THE STEAMER CAP.
  
 3) SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  