Plan Review Notes
Plan Review Notes For Permit 17030312
Permit Number 17030312
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-03-14 16:01:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1)
 SHEET G101 - THERE IS NO INDICATIONS REGARDING EXISTING
 LIFE SAFETY SYSTEMS.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PLEASE ENSURE ALL WORK IS PROPERLY SUBMITTED FOR
 PERMIT.
  
  
  
 2)
 SHEET E101 - THERE ARE CARD READERS AND STRIKE PLATES
 INDICATED.
  
 ALL CARD READER AND STRIKE PLATE WORK SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
  
  
 3)
 SHEET 201 - THRE ARE FIRE ALARM DEVICE/EQUIPMENT
 INDICATED.
  
 THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  