2017-03-14 16:01:06 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) |
| SHEET G101 - THERE IS NO INDICATIONS REGARDING EXISTING |
| LIFE SAFETY SYSTEMS. |
| |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| PLEASE ENSURE ALL WORK IS PROPERLY SUBMITTED FOR |
| PERMIT. |
| |
| |
| |
| 2) |
| SHEET E101 - THERE ARE CARD READERS AND STRIKE PLATES |
| INDICATED. |
| |
| ALL CARD READER AND STRIKE PLATE WORK SHALL BE |
| SUBMITTED UNDER SEPARATE SHOP DRAWINGS. |
| |
| |
| |
| 3) |
| SHEET 201 - THRE ARE FIRE ALARM DEVICE/EQUIPMENT |
| INDICATED. |
| |
| THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT |
| THE CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM SHALL BE DONE UNDER |
| SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY |
| CONTRACTORS. |
| |
| |
| |