2017-03-16 12:48:32PLANS ISSUED WITH THE FOLLOWING:
  
  
 PROVISO:
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22, 110.24
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405.5.2
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER