2017-03-22 17:19:043RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17030300
 3/22/17
  
 1) THE COOLING TOWER REPLACEMENT IS NOT PART OF THE
 SCOPE OF WORK FOR THIS PROJECT. PLEASE PROVIDE A PLAN
 THAT SPECIFICALLY ADDRSSES THE ROOF FANS ONLY. PLEASE
 NOTE THAT ALL PLANS MUST BEAR THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 2) IN LIEU OF SITE SPECIFIC ENGINEERING, THE NOA FOR
 THE ROOF FANS HAS BEEN SUBMITTED, HOWEVER THE DOCUMENT
 HAS NOT BEEN MARKED UP OR HIGHLIGHTED TO SHOW THE
 APPLICABLE INSTALLATION DETAILS FOR THE PROPOSED FAN
 AND CURB INSTALLATIONS- PLEASE COMPLY.
  