Plan Review Notes For Permit 17030300 |
Permit Number |
17030300 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-03-16 16:39:24 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17030300 | | 3/16/17 | | | | 1) PROVIDE LEGIBLE COPIES OF THE NOA #16-0209.05 THAT | | HAVE BEEN MARKED UP TO SHOW WHICH OF G SERIES FANS AND | | CURBS ARE TO BE INSTALLED, AND WHICH FASTENERS AND THE | | NUMBER OF EACH WILL BE USED TO ATTACH THE FANS TO THE | | CURBS, AND THE CURBS TO THE ROOF STRUCTURE. IF UNABLE | | TO PROVIDE THE ACCURATE INSTALLATION INFORMATION PER | | THE NOA, THEN PROVIDE WIND LOAD ENGINEERING BY A FL. | | LICENSE DESIGN PROFESSIONAL- SEE SECTION 301.15 FBC-14 | | MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. | | | | 2) AS PREVIOUSLY REQUESTED PROVIDE A ROOF PLAN SHOWING | | THE LOCATIONS OF THE FANS. THE COPIED FOUR JAYS | | CONSULTING PLAN FOR INSTALLATION OF THE COOLING TOWER | | IS NOT LEGIBLE AND NOT TO MINIMUM 1/8" SCALE AS | | REQUIRED BY SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. | | | | 3) PLEASE NOTE PER SECTION 107.1 THAT ALL PLANS, SPECS, | | NOA'S ETC. SHALL BE SUBMITTED IN DUPLICATE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|