2017-03-14 09:57:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030299
 3/14/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) IT APPEARS THAT A NEW AC IS BEING INSTALLED TO SERVE
 A PREVIOUSLY UNCONDITIONED SPACE WHICH REQUIRES
 COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION CODE.
 REFER TO SECTIONS C101.4.5 AND C401.2 AND SUBMIT ENERGY
 CALCULATIONS.
  
 3) THE SUBMITTED AC PLAN IS INDICATE 2200 CFMS OF
 SUPPLY AIR WHICH APPEARS TO EXCEED THE CAPACITY OF THE
 4-TON SYSTEM WHICH IS TYPICALLY 1600 CFMS.
  
 4) PROVIDE THE FOLLOWING ITEMS ON THE PLAN:
  
 A) AC EQUIPMENT SCHEDULE.
  
 B) DUCT SIZES.
  
 C) PRIMARY AND SECONDARY CONDENSATE DISPOSAL PLAN-
 SECTION 307 & 307.2.3
  
 D) AIR HANDLER INSTALLATION AND ACCESS DETAILS.
  
 E) STRUCTURAL DETAILS FOR INSTALLATION OF THE CONDENSER
 PAD AND ENGINEERING TO MOUNT THE CONDENSER TO THE PAD-
 SECTION 301.5
  
 5) PROVIDE ELECTRICAL PLANS.
  