Plan Review Notes
Plan Review Notes For Permit 17030255
Permit Number 17030255
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-10 09:53:21PLEASE SHOW AT METER LOCATION THAT THERE IS A 200MCB,
  
 ALSO SHOW ON PANEL SCHEDULE A, THE LOAD CALCULATION FOR
 PANEL B. THE 16,400WATT LOAD SHOWN AT PANEL B IS NOT
 ACCOUNTED FOR AT PANEL A CALCULATION.
  
 150A 2POLE SHOWN AT PANEL A BUT 100AMP FEDDERS AT
 #3THWN GOOD FOR 100AMPS ONLY. CORRECT TYPO TO REFLECT
 100A 2 POLE BREAKER. FBC 107.3.5
  
 V. PEREZ
 *6717