Plan Review Notes For Permit 17030255 |
Permit Number |
17030255 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-10 09:53:21 | PLEASE SHOW AT METER LOCATION THAT THERE IS A 200MCB, | | | | ALSO SHOW ON PANEL SCHEDULE A, THE LOAD CALCULATION FOR | | PANEL B. THE 16,400WATT LOAD SHOWN AT PANEL B IS NOT | | ACCOUNTED FOR AT PANEL A CALCULATION. | | | | 150A 2POLE SHOWN AT PANEL A BUT 100AMP FEDDERS AT | | #3THWN GOOD FOR 100AMPS ONLY. CORRECT TYPO TO REFLECT | | 100A 2 POLE BREAKER. FBC 107.3.5 | | | | V. PEREZ | | *6717 |
|