2017-03-20 13:12:35PASSED WITH PROVISO:
  
 PROVIDE REVISED AVAILABLE FAULT CURRENT CALCULATION FOR
 THE NEW SERVICE SHOWN AND LABEL SERVICE UPON FINAL
 INSPECTION WITH AIC. NEC 110.24A
  
 SITE LIGHT, YARD LIGHTS TO BE UNDER SEPERATE PERMIT.
 ANY LOW VOLTAGE AS WELL. FBC 107.3.5
  
 A SECOND MEANS OF GROUNDING REQUIRED TO SUPPLEMENT THE
 ONE GROUND ROD SHOWN. PROVIDE TWO RODS.
  