Notes |
Date |
Text |
2017-06-13 04:41:02 | 1) SUBMIT A COMPLETE WATER AND SANITARY RISER DIAGRAM | | FOR THE COMBINED UNIT "F".WPB AMEND. TO FBC SEC. | | 107.3.5.1.3. | | 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF "UNIT | | F". I LOOKED AT ALL THE FLOOR PLANS SUBMITTED ON THE | | ARCHITECTURAL SHEETS FOR THIS REVISION AND COULD NOT | | FIND ONE THAT SHOWED THE LOCATION OF THIS UNIT.IT IS | | VERY CONFUSING. WPB AMEND. TO FBC SEC. 107.2.1.WHAT | | UNITS/AREAS WERE COMBINED TO FORM UNIT F? INDICATE ON | | THE ENLARGED PLANS FOR UNIT F. WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|