Plan Review Notes
Plan Review Notes For Permit 17030213
Permit Number 17030213
Review Stop P
Sequence Number 1
Notes
Date Text
2017-04-28 11:08:201) SUBMIT AN EXPLANATION AS TO THE EXACT CHANGES THAT
 WERE DONE TO THE PLUMBING SHEETS ON THE SUMMARY OF
 ITEMS DOCUMENT THAT WAS SUBMITTED.WPB AMEND. TO FBC
 SEC. 107.2.1
 2) .SUBMIT REVISED SANITARY AND WATER RISER DIAGRAMS
 FOR ALL CHANGES MADE TO THE PLUMBING SYSTEMS UNDER THIS
 REVISION. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 3) SUBMIT AN EXPLANATION AS TO THE EXACT CHANGES THAT
 WERE DONE TO THE DRAINAGE SYSTEM ON SHT.# C103.
 4) THE SUBMITTED NARRRATIVE FOR THIS REVISION PROVIDES
 NO CLEAR EXPLANATION AS TO THE CHANGES THAT HAVE BEEN
 DONE TO EACH SHEET. PROVIDE A NARRATIVE THAT CLEALY
 DESCRIBES THE CHANGES THAT HAVE BEEN MADE TO EACH PLAN
 AND THOSE CHANGES SHALL BE CLEARLY IDENTIFIED ON THE
 PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 5) PLACE INFORMATION ON THE ARCHITECTURAL PLANS THAT
 THIS IS PHASE ONE OF THE PROJECT. WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SOLIDS
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P413 - THE SINK AT THE OUTDOOR KITCHEN SHALL
 DISCHARGE INDIRECTLY TO THE GI-2 INTERCEPTOR PER 2010
 FBC SEC.802.1.8.
 8) SHT. P413 - KITCHEN EQUIPMENT (ICE, COFFEE, STEAMER,
 BEVERAGE DISPENSER) SHALL BE EQUIPPED WITH BACKFLOW
 PREVENTERS PER 2010 FBC-PLUMBING SECS.608.16.1,
 608.16.10.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  