Plan Review Notes
Plan Review Notes For Permit 17030134
Permit Number 17030134
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-07 10:57:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SUBMIT A REVISED LOAD CALCULATION FOR NEW
 50AMP SHOWN FED FROM 400AMP SERVICE
 2. NOTE THAT MODIFICATION DONE TO ELECTRICAL SERVICE
 WILL REQUIRE A REVISED FAULT CURRENT CALCULATION AT
 SERVICE PER NEC 110.24B. A NOTE WILL SUFFICE.
 3. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  
  
  
  