Plan Review Notes For Permit 17030084 |
Permit Number |
17030084 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-10 11:37:54 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE PROVIDE AND REFLECT ON ELECTRICAL DRAWINGS | | THE ELECTRICAL DATA INFORMATION, EXAMPLE VOLTAGE, TOTAL | | AMPS, CIRCUITS POWER SUPPLY INFORMATION ETC. FBC | | 107.3.5- MINIMUM PLAN REVIEW CRITERIA | | 2. ADD GENERAL NOTES TO INDICATE THAT ALL MATERIALS AND | | FASTENERS MEET 3004.4 | | 3. ALL ELECTRICAL COMPONENTS ARE UL LISTED AND APPROVED | | (GENERAL NOTE) | | 4. SIGN TO BE GROUNDED ACCORDING TO NEC 600.7 (GENERAL | | NOTE) | | 5. SIGN TO BE MANUFACTURED AND LISTED NEC 600.3 AND | | MARKED PER NEC 600.4(GENERAL NOTE) | | 6. ALL BRANCH CIRCUITS PER NEC 600.5(B)1 AND B2(GENERAL | | NOTE) | | 7. SIGN TO BE CONTROLLED BY PHOTOCELL OR TIME CLOCK PER | | FBC 2014 ENERGY CONSERVATION C405.2.4(GENERAL NOTE) | | 8. VISIBLE 20AMP DISCONNECT PER SIGN PER CIRCUIT NEC | | 600.6 A1 AND 2. (GENERAL NOTE) | | 9. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | | | | | |
|