Plan Review Notes
Plan Review Notes For Permit 17030084
Permit Number 17030084
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-10 11:37:54INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE AND REFLECT ON ELECTRICAL DRAWINGS
 THE ELECTRICAL DATA INFORMATION, EXAMPLE VOLTAGE, TOTAL
 AMPS, CIRCUITS POWER SUPPLY INFORMATION ETC. FBC
 107.3.5- MINIMUM PLAN REVIEW CRITERIA
 2. ADD GENERAL NOTES TO INDICATE THAT ALL MATERIALS AND
 FASTENERS MEET 3004.4
 3. ALL ELECTRICAL COMPONENTS ARE UL LISTED AND APPROVED
 (GENERAL NOTE)
 4. SIGN TO BE GROUNDED ACCORDING TO NEC 600.7 (GENERAL
 NOTE)
 5. SIGN TO BE MANUFACTURED AND LISTED NEC 600.3 AND
 MARKED PER NEC 600.4(GENERAL NOTE)
 6. ALL BRANCH CIRCUITS PER NEC 600.5(B)1 AND B2(GENERAL
 NOTE)
 7. SIGN TO BE CONTROLLED BY PHOTOCELL OR TIME CLOCK PER
 FBC 2014 ENERGY CONSERVATION C405.2.4(GENERAL NOTE)
 8. VISIBLE 20AMP DISCONNECT PER SIGN PER CIRCUIT NEC
 600.6 A1 AND 2. (GENERAL NOTE)
 9. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  
  