2017-03-09 15:10:342300 PRESIDENTIAL WAY - CONSTRUCTION TRAILER COMPOUND
 PERMIT #17030022
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON THE PLANS.
  
 PROVIDE A LEGIBLE AND DETAILED SITE PLAN. THE CURRENT
 PLAN IS OVERLAID AND IS VERY DIFFICULT TO READ AND
 UNDERSTAND EXACT TRAILER LOCATIONS.
  
 THE PLANS INDICATE ONE TYPICAL FLOOR PLAN WILL BE USED
 FOR ALL THREE TRAILER COMPOUNDS. CONFIRM THIS IS
 ACCURATE.
  
 NO PORTABLE FIRE EXTINGUISHERS PROVIDED. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO STAIR, HANDRAIL, OR GUARDRAIL DETAILS SUBMITTED.
  
 EACH TRAILER INDICATES A PRIMARY AND SECONDARY EXIT;
 HOWEVER, NO EXIST DISCHARGE INFORMATION IS PROVIDED.
  
 PLANS INDICATE AN ADA RAMP; HOWEVER, THESE RAMPS CANNOT
 BE LOCATED ON THE SITE PLAN.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF 150
 FEET IN LENGTH SHALL BE PROVIDED WITH APPROVED
 PROVISIONS FOR THE FIRE APPARATUS TO TURN AROUND. PER
 SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS
 ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 PLANS DO NOT INDICATE ANY NEW OR EXISTING FIRE HYDRANTS
 TO PROTECT THE TRAILER COMPOUND.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  