2017-03-09 15:10:34 | 2300 PRESIDENTIAL WAY - CONSTRUCTION TRAILER COMPOUND |
| PERMIT #17030022 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NO ADDRESS PROVIDED ON THE PLANS. |
| |
| PROVIDE A LEGIBLE AND DETAILED SITE PLAN. THE CURRENT |
| PLAN IS OVERLAID AND IS VERY DIFFICULT TO READ AND |
| UNDERSTAND EXACT TRAILER LOCATIONS. |
| |
| THE PLANS INDICATE ONE TYPICAL FLOOR PLAN WILL BE USED |
| FOR ALL THREE TRAILER COMPOUNDS. CONFIRM THIS IS |
| ACCURATE. |
| |
| NO PORTABLE FIRE EXTINGUISHERS PROVIDED. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| NO STAIR, HANDRAIL, OR GUARDRAIL DETAILS SUBMITTED. |
| |
| EACH TRAILER INDICATES A PRIMARY AND SECONDARY EXIT; |
| HOWEVER, NO EXIST DISCHARGE INFORMATION IS PROVIDED. |
| |
| PLANS INDICATE AN ADA RAMP; HOWEVER, THESE RAMPS CANNOT |
| BE LOCATED ON THE SITE PLAN. |
| |
| PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN |
| TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE |
| PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE |
| PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| JURISDICTION. |
| |
| THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION |
| TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO |
| "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION |
| REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION |
| TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND |
| COMPLIANCE WITH THE FOLLOWING: |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF 150 |
| FEET IN LENGTH SHALL BE PROVIDED WITH APPROVED |
| PROVISIONS FOR THE FIRE APPARATUS TO TURN AROUND. PER |
| SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS |
| ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE |
| APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL |
| HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND |
| AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| FEET 6 INCHES. |
| |
| PLANS DO NOT INDICATE ANY NEW OR EXISTING FIRE HYDRANTS |
| TO PROTECT THE TRAILER COMPOUND. |
| |
| A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED DURING PLAN RESUBMISSION. |
| |