2017-03-16 07:28:16 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17030022 |
| ADD: 2300 PRESIDENTIAL WAY |
| CONT: HEDRICK BROTHERS |
| TEL: 561-689-0880 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. MARCH 16/ 2017 |
| ACTION: DENIED |
| |
| 1) SITE PLAN: |
| 1A) THE SITE PLAN IS BLOWN UP SO LARGE THE LOCATION |
| CANNOT BE VERIFIED AS TO THE LOCATION AND ADDRESS. SITE |
| PLAN INDICATES BANYAN CAY RESORT BUT THE PERMIT |
| APPLICATION INDICATES 2300 PRESIDENTIAL WAY. 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED. |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, |
| FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD |
| ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| ACCURATE BOUNDARY LINE SURVEY. |
| |
| 1B) THE SITE PLAN SHOWS (3) ACCESSIBLE PARKING SPACES |
| AND ACCESS AISLES BUT THERE ARE NO DETAILS SHOWING |
| COMPLIANCE WITH ANY ACCESSIBLE ELEMENTS OF EITHER THE |
| ACCESSIBLE PARKING SPACE NOR THE ACCESS AISLE. |
| 2014 FBC-ACCESS. CODE PARKING SECTION 502.1-502.7. |
| |
| 2) THE SUBMITTED PLANS AND MODULAR UNIT WERE DESIGNED |
| TO THE 1997 SBBCI WITH A WIND SPEED OF 110 MPH FASTEST |
| MILE. OUR CURRENT CODE IS DESIGNED TO 170 VULT 3 SECOND |
| GUST. PLEASE SHOW THE RELATIONSHIP IN WIND SPEEDS AND |
| HOW COMPLIANCE WITH THE 2014 EXISTING BUILD. CODE |
| SECTION 1302.3 WIND LOADS MAKE COMPLIANCE. [B] 1302.3 |
| WIND LOADS. BUILDINGS SHALL COMPLY WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| EXCEPTIONS: |
| 2. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT INCREASED BY |
| MORE THAN 10 PERCENT. |
| 3. MANUFACTURED BUILDINGS AS APPROVED BY THE |
| MANUFACTURED BUILDINGS PROGRAM, FLORIDA DEPARTMENT OF |
| BUSINESS AND PROFESSIONAL REGULATION. |
| YOU CAN INTERPOLATE BETWEEN CONTROL LINES. |
| |
| 3) SHEET A1 SHOW EACH MANUFACTURED BUILDING WILL HAVE 2 |
| EXITS. THE SITE PLAN ONLY SHOWS RAMPS AT THE MAIN EXIT, |
| THERE HAS BEEN NO CONSIDERATION HOW THE SECONDARY EXIT |
| WILL BE ACHIEVED? FBC-B 2027.1. |
| EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE |
| BUILDING. THE EXIT DISCHARGE SHALL BE AT GRADE OR SHALL |
| PROVIDE DIRECT ACCESS TO GRADE. SHEET RS-1 SHOWS |
| DETAILS FOR AN ACCESSIBLE RAMP BUT NO STAIR NOR LANDING |
| DETAILS. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
2017-03-10 15:14:51 | RESULTED BY MISTAKE JLEAHY |