Plan Review Notes For Permit 17030014 |
Permit Number |
17030014 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-05-11 15:59:01 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SOME OF THE INFORMATION ON THE PLANS THAT WERE | | SUBMITTED IS ILLEGIBLE. FBC 107.2.1 | | | | 2) THE RETURN AIR FOR THE LIBRARY IS CONNECTED TO THE | | AIR HANDLER THAT DOES NOT SUPPLY AIR TO THE ROOM. THE | | SUPPLY AND RETURN AIR NEED TO BE FROM THE SAME SYSTEM. | | FBCR-M1601 | | | | 3) THERE ARE SOME DISCREPANCIES BETWEEN THE EQUIPMENT | | SIZING CALCULATIONS, THE PLANS AND ENERGY FORM | | R405-2014. THE FORM R405-2014 HAS 17,000 BTU OF HEAT | | FOR THE #2 SYSTEM AND THE ENERGY CALCULATIONS HAS | | 25,500 BTU. THE PLANS SPECIFY 10 KW FOR THE HEAT ON | | SYSTEM #2 AND THE ENERGY CALCULATIONS SPECIFY 7.5 KW. | | THE MODEL NUMBERS FOR THE EQUIPMENT ON THE PLANS DO NOT | | MATCH THE ONES LISTED ON THE ENERGY CALCULATIONS. FBC | | ENERGY CONSERVATION R-403.6 | | | | | | | | |
|