2017-05-11 15:59:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SOME OF THE INFORMATION ON THE PLANS THAT WERE
 SUBMITTED IS ILLEGIBLE. FBC 107.2.1
  
 2) THE RETURN AIR FOR THE LIBRARY IS CONNECTED TO THE
 AIR HANDLER THAT DOES NOT SUPPLY AIR TO THE ROOM. THE
 SUPPLY AND RETURN AIR NEED TO BE FROM THE SAME SYSTEM.
 FBCR-M1601
  
 3) THERE ARE SOME DISCREPANCIES BETWEEN THE EQUIPMENT
 SIZING CALCULATIONS, THE PLANS AND ENERGY FORM
 R405-2014. THE FORM R405-2014 HAS 17,000 BTU OF HEAT
 FOR THE #2 SYSTEM AND THE ENERGY CALCULATIONS HAS
 25,500 BTU. THE PLANS SPECIFY 10 KW FOR THE HEAT ON
 SYSTEM #2 AND THE ENERGY CALCULATIONS SPECIFY 7.5 KW.
 THE MODEL NUMBERS FOR THE EQUIPMENT ON THE PLANS DO NOT
 MATCH THE ONES LISTED ON THE ENERGY CALCULATIONS. FBC
 ENERGY CONSERVATION R-403.6
  
  
  
  