Plan Review Notes
Plan Review Notes For Permit 17030014
Permit Number 17030014
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-15 15:20:141ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. MASTER BATH TUB IS MISSING ON PLUMBING RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 2. BAR SINK IN GREAT ROOM IS MISSING ON THE RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 3. THE WASHING MACHINE CAN NOT CONNECT TO THE BATHROOM
 GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM OF
 THE BATHROOM GROUP. PER FBC RES P3108.1
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  