Plan Review Notes For Permit 17030014 |
Permit Number |
17030014 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-15 15:20:14 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. MASTER BATH TUB IS MISSING ON PLUMBING RISER. PER | | WPB AMEND TO FBC 107.2.1 | | | | 2. BAR SINK IN GREAT ROOM IS MISSING ON THE RISER. PER | | WPB AMEND TO FBC 107.2.1 | | | | 3. THE WASHING MACHINE CAN NOT CONNECT TO THE BATHROOM | | GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM OF | | THE BATHROOM GROUP. PER FBC RES P3108.1 | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|