2017-09-20 15:47:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 2 PANELS, THERE IS NO PANEL
 INDICATED FOR CABANA, AND I SEE NO CIRCUIT DESIGNATED
 FOR CABANA. BE ADVISED THAT A SEPARATE STRUCTURE IS
 PERMITTED TO BE FED BY ONLY ONE CIRCUIT, WHICH IN THIS
 CASE WOULD TYPICALLY BE A SUB-PANEL. "A BUILDING OR
 OTHER STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR
 FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING
 MEANS SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH
 CIRCUIT. NEC 225.30". PROVIDE CORRECTION.
 2. PROVIDE CORRECTED RISER DIAGRAM SHOWING THE
 GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING
 OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT.
 NEC 250.32; FBC RE3607.3
 3. IF A SUB-PANEL IS INSTALLED IN CABANA, PROVIDE PANEL
 SCHEDULE FOR THIS PANEL, INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. ADDITIONALLY, SHOW LOCATION OF PANEL ON
 PLAN. FBC 107.2.1; NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR CABANA PANEL. NEC 225.31,
 225.32
 5. NO HVAC EQUIPMENT IS SHOWN ON THE ELECTRICAL PLAN
 FOR CABANA. PROVIDE DETAILS ON PLAN, SHOW REQUIRED GFCI
 PROTECTED OUTLET FOR SERVICING THE EQUIPMENT. NEC
 210.63; FBC RE3901.12; FBC 107.2.1
 6. RISER SHOWS PVC SCHEDULE 40 FOR THE CONDUIT
 SUPPLYING THE FPL FEED. THIS CONDUIT IS REQUIRED TO BE
 SCHEDULE 80 PVC, OR ANOTHER APPROVED TYPE. PROVIDE
 CORRECTION. NEC 300.5(D)(4); FBC RE 3802.3.2
 7. RISER SHOWS THE GROUNDING ELECTRODE CONDUCTOR SIZED
 AS #4. THE MINIMUM SIZE REQUIRED PER CODE IS 1/0
 COPPER. PROVIDE CORRECTION. FBC RE TABLE T3603.1
 8. PROVIDE ONE ACCURATE LOAD CALCULATION FOR ENTIRE
 SERVICE. IT APPEARS THAT THERE ARE LOAD CALCULATIONS
 FOR THE 2 PANELS, BUT NOT ALL LOADS ARE INCLUDED.
 PROVIDE CORRECTION. NEC 220.82; FBC RE 3602.2
 9. INDICATE GFCI PROTECTION FOR ALL OUTSIDE WP OUTLETS
 PER PREVIOUS COMMENT. NOTHING IN THE LEGEND STATES THAT
 A WP RECEPTACLE IS ALSO GFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.8; FBC RE 3902.3
 10. THERE ARE NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS.
 WILL THESE BE INSTALLED? IF SO, SHOW GFCI PROTECTED
 OUTLETS. NEC 210.8; FBC RE 3902.2
 11. THERE IS A ROOM ADJACENT TO THE MASTER BATH THAT
 APPEARS TO BE A CLOSET, ALTHOUGH IT IS NOT LABELED ON
 PLAN. IN THIS AREA, A LIGHT IS SHOWN DIRECTLY ABOVE THE
 SHELVING. PROVIDE CORRECTION. ALSO, PROVIDE NOTE THAT
 ALL CLOSET LIGHTING WILL COMPLY WITH NEC 410.16. NEC
 410.16; FBC RE4003.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  