Date |
Text |
2017-09-20 15:47:31 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM SHOWS 2 PANELS, THERE IS NO PANEL |
| INDICATED FOR CABANA, AND I SEE NO CIRCUIT DESIGNATED |
| FOR CABANA. BE ADVISED THAT A SEPARATE STRUCTURE IS |
| PERMITTED TO BE FED BY ONLY ONE CIRCUIT, WHICH IN THIS |
| CASE WOULD TYPICALLY BE A SUB-PANEL. "A BUILDING OR |
| OTHER STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR |
| FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING |
| MEANS SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH |
| CIRCUIT. NEC 225.30". PROVIDE CORRECTION. |
| 2. PROVIDE CORRECTED RISER DIAGRAM SHOWING THE |
| GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING |
| OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT. |
| NEC 250.32; FBC RE3607.3 |
| 3. IF A SUB-PANEL IS INSTALLED IN CABANA, PROVIDE PANEL |
| SCHEDULE FOR THIS PANEL, INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. ADDITIONALLY, SHOW LOCATION OF PANEL ON |
| PLAN. FBC 107.2.1; NEC 210.8, 210.12, 215.5, 408.4; FBC |
| RE3706.2, RE3902 |
| 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR CABANA PANEL. NEC 225.31, |
| 225.32 |
| 5. NO HVAC EQUIPMENT IS SHOWN ON THE ELECTRICAL PLAN |
| FOR CABANA. PROVIDE DETAILS ON PLAN, SHOW REQUIRED GFCI |
| PROTECTED OUTLET FOR SERVICING THE EQUIPMENT. NEC |
| 210.63; FBC RE3901.12; FBC 107.2.1 |
| 6. RISER SHOWS PVC SCHEDULE 40 FOR THE CONDUIT |
| SUPPLYING THE FPL FEED. THIS CONDUIT IS REQUIRED TO BE |
| SCHEDULE 80 PVC, OR ANOTHER APPROVED TYPE. PROVIDE |
| CORRECTION. NEC 300.5(D)(4); FBC RE 3802.3.2 |
| 7. RISER SHOWS THE GROUNDING ELECTRODE CONDUCTOR SIZED |
| AS #4. THE MINIMUM SIZE REQUIRED PER CODE IS 1/0 |
| COPPER. PROVIDE CORRECTION. FBC RE TABLE T3603.1 |
| 8. PROVIDE ONE ACCURATE LOAD CALCULATION FOR ENTIRE |
| SERVICE. IT APPEARS THAT THERE ARE LOAD CALCULATIONS |
| FOR THE 2 PANELS, BUT NOT ALL LOADS ARE INCLUDED. |
| PROVIDE CORRECTION. NEC 220.82; FBC RE 3602.2 |
| 9. INDICATE GFCI PROTECTION FOR ALL OUTSIDE WP OUTLETS |
| PER PREVIOUS COMMENT. NOTHING IN THE LEGEND STATES THAT |
| A WP RECEPTACLE IS ALSO GFCI PROTECTED. PROVIDE |
| CORRECTION. NEC 210.8; FBC RE 3902.3 |
| 10. THERE ARE NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS. |
| WILL THESE BE INSTALLED? IF SO, SHOW GFCI PROTECTED |
| OUTLETS. NEC 210.8; FBC RE 3902.2 |
| 11. THERE IS A ROOM ADJACENT TO THE MASTER BATH THAT |
| APPEARS TO BE A CLOSET, ALTHOUGH IT IS NOT LABELED ON |
| PLAN. IN THIS AREA, A LIGHT IS SHOWN DIRECTLY ABOVE THE |
| SHELVING. PROVIDE CORRECTION. ALSO, PROVIDE NOTE THAT |
| ALL CLOSET LIGHTING WILL COMPLY WITH NEC 410.16. NEC |
| 410.16; FBC RE4003.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |