Plan Review Notes For Permit 17030007 |
Permit Number |
17030007 |
|
Review Stop |
NFIP |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-26 14:28:47 | PROVISO | | BASE FLOOD ELEVATION FOR ZONE A5 IS 7.0 FEET. REQUIRED | | FREEBOARD IS 12 INCHES. DESIGN FLOOD ELEVATION OF 8.0 | | FEET IS CORRECT. | | SEPERATE ELEVATION CERTIFICATES HAVE BEEN PROVIDED FOR | | MAIN HOUSE AND CABANA. | | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD. | | | | GARAGE FINISHED FLOOR ELEVATION IS SET AT 7.7 FEET. | | FLOOD OPENINGS REQUIRED. PROVIDE COPY OF PRE-ENGINEERED | | FLOOD VENTS AT TIME OF INSPECTION. | | | | AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | RECOMMENDED. | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | REQUIRED FOR BOTH STRUCTURES AND SHALL BE SUBMITTED FOR | | REVIEW AND APPROVAL PRIOR TO THE ISSUANCE OF THE | | CERTIFICATE OF OCCUPANCY. | | | | |
|