Plan Review Notes
Plan Review Notes For Permit 17030007
Permit Number 17030007
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-07 17:52:34PLAN DENIED
 1) NEED DUCT SIZE ON 2ND FLOOR RETURN AIR DUCT 107 FBC
 2014
 2) SHOW DRYER EXHAUST ON PLAN. PER SECTION M1502.3 FBC
 2014
 3) PROVIDE TOTAL CFM FOR EACH UNIT ON PLANS. PER 107
 FBC
 4) PROVIDE MORE INFORMATION ON RETURN AIR PLENUM'S
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676