Plan Review Notes
Plan Review Notes For Permit 17030007
Permit Number 17030007
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-21 08:58:13INITIAL PLAN REVIEW ELECTRICAL 3/20/2017
  
 2814 N FLAGLER DR
 PERMIT 17030007
  
  
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
  
 COMMENTS:
  
 1) PAGE A-6 SEPARATE STRUCTURE SHALL COMPLY WITH
 225.30, 225.31, 225.32, E3607.3 FBC RESIDENTIAL
 2) PAGE E-1 GENERAL OUTLET SPACING TO MEET E-3901.2,
 E3901.2.1 FBC RESIDENTIAL
 3) GARAGE SHOWS NO OUTLETS E3901.9 FBC RESIDENTIAL
 4) LOAD NOT SHOWN FOR ELEVATOR
 5) DRYER LOAD IS 5000W MINIMUM
 6) NO CIRCUITS SHOWN FOR WASHER AND DRYER
 7) RISER DIAGRAM SHOS ONLY ONE PANEL
 8) OUTLETS IN THE OPEN AREA ON GROUND FLOOR SHALL BE
 GFCI PROTECTED
 9) A SEPARATE PLAN AND PERMIT WILL BE REQUIRED FOR LV
 SYSTEMS IF NOT SHOWN ON PLANS.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  
  
  