2017-04-10 14:27:23 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1. SEPERATE PERMIT REQUIRED FOR ACCESSORY STRUCTURE |
| (CABANA). STATED VALUE MAY BE PRORATED BETWEEN |
| STRUCTURES. |
| |
| 2. THIS REVIEW IS ONLY FOR THE MAIN RESIDENCE. A REVIEW |
| OF THE CABANA MAY GENERATE ADDITIONAL COMMENTS. |
| |
| 3. PALM BEACH COUNTY IMPACT FEES REQUIRED. |
| |
| 4. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS |
| FOR NEW ROOFING SYSTEM COMPONENTS. |
| |
| 5. THIS PROPERTY LIES IN FLOOD ZONE A5. BASE FLOOD |
| ELEVATION IS 7.5 FT. CORRECT FLOOD ZONE NOTE ON SURVEY. |
| FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) & |
| R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND |
| STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS |
| COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED |
| TO 6 INCHES ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE |
| FLOOD DESIGN INFORMATION ON THE PROPOSED SURVEY AND |
| PROVIDE FLOOD ELEVATION CERTIFICATE. |
| |
| G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. |
| FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION |
| SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO |
| THE FOLLOWING: |
| |
| 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY |
| WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS |
| TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF |
| FLOODWATERS. |
| |
| SECTION R322 FLOOD-RESISTANT CONSTRUCTION |
| R322.1 GENERAL. |
| BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN |
| PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS |
| ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND |
| CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED |
| IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN |
| WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE |
| DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24. |
| |
| FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, |
| FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE |
| DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE |
| SURVEY. |
| |
| 6. ELEVATION CERTIFICATE REQUIRED AT PERMITTING AND |
| PRIOR TO C.O. |
| |
| 1612.5 FLOOD HAZARD DOCUMENTATION. |
| THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND |
| SEALED BY A REGISTERED DESIGN PROFESSIONAL AND |
| SUBMITTED TO THE BUILDING OFFICIAL: |
| |
| 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN |
| COASTAL HIGH HAZARD AREAS: |
| |
| 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING |
| BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND |
| THE FINAL INSPECTION IN SECTION 110.3. |
| |
| 7. GEOTECHNICAL REPORT BY ALLTERRA PROVIDES TWO |
| FOUNDATION ALTERNATIVES. PLANS SPECIFY DEEP FOUNDATION |
| ALTERNATIVE SHALL BE USED. PROVIDE CERTIFICATION LETTER |
| FROM ALLTERRA UPON COMPLETION OF DEEP FOUNDATION. |
| |
| 8. PROVIDE SHOP DRAWINGS FOR ELEVATOR. |