Plan Review Notes For Permit 17021226 |
Permit Number |
17021226 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-08 12:51:36 | 1) THE DESCRIPTION OF WORK ON THE PERRMIT APPLICATION | | NOTES TWO SEPARATE SYSTEMS: ONE FOR THE GROUND FLOOR | | AND ONEE FOR THE THE 7TH FLOOR. THERE IS ONLY ONE PLAN | | WHICH IS FOR THE POOL TERRACE WHICH APPEARS TO BE | | LOCATED ON THE 7TH FLOOR. CLARIFY. SUBMIT TWO COMPLETE | | SETS OF PLANS FOR BOTH SYSTEMS. WPB AMEND. TO FBC SEC. | | 107.1. | | 2) IDENTIFY ALL THE PIPING AND HEADS THAT WILL BE | | INSTALLED BY HILITING. WPB AMEND. TO FBC SEC. 107.2.1. | | THE PLANS SHOW SOME AREAS OF HEADS AND PIPING HILITED | | AND SOME AREAS NOT. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|