2017-03-01 07:35:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17021190
 ADDRESS: 5089 N. MILITARY TRAIL SOUTH OBSERVATION TOWER
 CONT: THERMA SEAL ROOFING SYSTEMS, LLC
 TEL: 561-223-2096
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. MARCH 01/ 2017
 ACTION: DENIED
  
 1) THE FLORIDA APPROVAL 16758-R7 JOHN MANVILLE TPO ROOF
 COVERING APPENDIX A INSTALLATION DETAILS THE BOTTOM
 RIGHT FASTENER PATTERN IS CIRCLED WITH THE NOTATION SEE
 ENGINEERING FOR CORNERS AND PERIMETER ZONES. PLEASE
 NOTE THERE IS NO ENGINEERING SUBMITTED WITHIN THIS
 PERMIT PACKAGE. SEE LIMITATION # 7 ENHANCED FASTENING
 IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES
 SHALL BE INCREASED FOR BOTH INSULATION & OR THE BASE
 SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING
 APPLICATION STANDARDS RAS 117. CALCULATION PREPARED,
 SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER