2017-03-01 07:35:19 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17021190 |
| ADDRESS: 5089 N. MILITARY TRAIL SOUTH OBSERVATION TOWER |
| CONT: THERMA SEAL ROOFING SYSTEMS, LLC |
| TEL: 561-223-2096 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: WED. MARCH 01/ 2017 |
| ACTION: DENIED |
| |
| 1) THE FLORIDA APPROVAL 16758-R7 JOHN MANVILLE TPO ROOF |
| COVERING APPENDIX A INSTALLATION DETAILS THE BOTTOM |
| RIGHT FASTENER PATTERN IS CIRCLED WITH THE NOTATION SEE |
| ENGINEERING FOR CORNERS AND PERIMETER ZONES. PLEASE |
| NOTE THERE IS NO ENGINEERING SUBMITTED WITHIN THIS |
| PERMIT PACKAGE. SEE LIMITATION # 7 ENHANCED FASTENING |
| IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES |
| SHALL BE INCREASED FOR BOTH INSULATION & OR THE BASE |
| SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING |
| APPLICATION STANDARDS RAS 117. CALCULATION PREPARED, |
| SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| ENGINEER OR REGISTERED ARCHITECT. |